Contents - Index


Strip-fin plate-fin, surface 1/9-25.01

 

 

Procedure Compact_HX_ND('sf_plate-fin_s19-2501', Re: f,j_H) is a non-dimensional procedure that returns the friction factor and the Colburn j factor for external flow through strip-fin plate-fins with surface 1/9-25.01 given the Reynolds number. The values calculated are based on a best fit curve to experimental data. These data are from Kays and London (1984) p. 244.   

 

Related procedures include:

Geometry-(more info)

CHX_geom_plate_fin('sf_plate-fin_s19-2501', a, b_2: b_1, D_o, fin_pitch, D_h, fin_thk, sigma, alpha, A_fin\A)

Coefficient of heat transfer-(more info)

CHX_h_plate_fin('sf_plate-fin_s19-2501', a, b_2, m_dot, A_fr, Fluid$,T, P:h)

Pressure drop-(more info)

CHX_DELTAp_plate_fin('sf_plate-fin_s19-2501', a, b_2, m_dot, A_fr, L, Fluid$, T_i, T_o, P: DELTAp)

 

Additional Information

Fin pitch = 985 per m

Plate spacing, b = 5.08e-3 m

Fin length = 2.8e-3 m

D_h = 1.50e-3 m

Fin metal (aluminum) thickness = 0.102e-3 m

Total heat transfer area/volume between plates(Beta) = 2360 m^2/m^3

Fin area/total area = 0.881

 

 

Compact Heat Exchangers Index