Contents - Index


Finned flat tubes, surface 9.29-0.737-SR

 

 

Procedure Compact_HX_ND('ff_tubes_s929-0737-SR', Re: f,j_H) is a non-dimensional procedure that returns the friction factor and the Colburn j factor for external flow through finned flat tubes with surface 9.29-0.737-SR given the Reynolds number. The values calculated are based on a best fit curve to experimental data. These data are from Kays and London (1984) p. 272.   

 

Related procedures include:

Geometry-(more info)

CHX_geom_finned_tube('ff_tubes_s929-0737-SR': D_o, fin_pitch, D_h, fin_thk, sigma, alpha, A_fin\A)

Coefficient of heat transfer-(more info)

CHX_h_finned_tube('ff_tubes_s929-0737-SR', m_dot, A_fr, Fluid$,T, P:h)

Pressure drop-(more info)

CHX_DELTAp_finned_tube('ff_tubes_s929-0737-SR', m_dot, A_fr, L, Fluid$, T_i, T_o, P: DELTAp)

 

Additional Information

Fin pitch = 366 per m

D_h = 4.12e-3 m

Fin metal (copper) thickness = 0.102e-3 m

sigma=0.788

Heat transfer area/total volume (alpha) =748 m^2/m^3

Fin area/total area = 0.814

 

 

Compact Heat Exchangers Index