Contents - Index


R513B

 

R513B is an azeotropic mixture consisting of 12 weight% R32, 58.5% R1234yf and 41.5% R234a.  It is currently marketed by Daikin and considered to be a replacement fluid for R134a.  It has a molar mass of 108.74 kg/kmol.  

 

Thermodynamic data for R513B are provided using a pseudo-pure fluid model in the manner described by: 

 

E. Lemmon

"Pseudo-Pure Fluid Equations of State for the Refrigerant Blends R-410A, R-404A,R-507A, and R-407C"

International Journal of Thermophysics, Vol. 24, No. 4, July 2003

 

The generalized equation of state was fitted by F-Chart Software using thermodynamic property data provided by the REFPROP 10 program.   The reference state for enthalpy and entropy is the IIR recommendation in which the specific enthalpy and entropy of saturated liquid are 200 kJ/kg and 1.0 kJ/kg-K, respectively.  The model is applicable for temperatures between 200 K and 420 K with pressures up to 20 MPa.  

 

Transport properties are estimated using a corresponding states approach as suggested in:

 

Klein, S.A., McLinden, M.O., and Laesecke , A., "An improved extended corresponding states method for estimation of viscosity of pure refrigerants and mixtures",  Int. J. of Refrigeration, 20, pp. 208-217, 1997

 

McLinden et al., "An extended corresponding states model for the thermal conductivity of refrigerants and refrigerant mixtures", Int. J. of Refrigeration, 23, pp. 43-63, 2000

 

 

Fluid Property Information